Emissivity, Reflected Temperature and Load: Getting Electrical IR Readings Right

Why shiny metal lies, how to measure reflected temperature, and the field habits that make an electrical IR reading defensible.

A thermal camera does not measure temperature. It measures infrared energy and calculates a temperature from the settings you give it. Get the settings wrong and the camera still prints a confident number to one decimal place.

In short
  • Measure on high-emissivity surfaces (insulation, paint, tape), not on bare shiny metal.
  • Set reflected temperature, and move to check that a hot spot is not a reflection.
  • Get close enough that the hot part covers several pixels.
  • Record load, and wind and sun for outdoor gear.

Emissivity: how well a surface radiates

Emissivity runs from 0 to 1 and says how much infrared energy a surface gives off compared with a perfect emitter at the same temperature. In electrical work the split is simple:

  • High and predictable: painted surfaces, conductor insulation, electrical tape, heavily oxidized metal. Typically 0.9 or above.
  • Low and unpredictable: clean copper, polished bus bar, tin-plated lugs, bare aluminium. Low emissivity also means high reflectivity, so these surfaces show their surroundings as much as themselves.

On a connection that is hotter than its surroundings, a shiny surface usually reads low, so the real problem is worse than the image suggests. The practical fix is to measure where the surface is predictable: the insulation right where the conductor enters the lug, a painted part of the breaker body, a label. When emissivity really matters, ASTM E1933 sets out field methods for measuring it.

Reflected temperature: what the surface is mirroring

Every surface reflects some infrared energy from what is around it, and the lower its emissivity, the more it reflects. The camera's reflected-temperature setting removes that contribution, so it should match what the target actually sees: a room at 20 °C, a hot transformer beside it, the sky outdoors.

ASTM E1862 gives two procedures. The common field one is the reflector method: crumple a piece of aluminium foil, flatten it, hold it where the target is, set the camera to an emissivity of 1.0 and read the foil's average apparent temperature. That is your reflected temperature.

Spotting a reflection

Light fixtures, the sun, nearby hot equipment and your own body all show up in shiny metal. Change your angle: a reflection moves across the surface as you move; a real hot spot stays on the part.

Distance and spot size

Each pixel covers a patch of the scene that grows with distance. A small target, such as a fuse clip or a terminal screw, seen from too far away shares its pixels with cooler surroundings, and the camera averages them. The hot spot reads low or disappears. Get closer, within your safe approach distance, or use a longer lens, until the hot part covers several pixels.

Load, wind and sun

Heat at a resistive connection rises with the square of the current, so scan under normal load where you can. NFPA 70B guidance is no less than 40% of normal circuit loading, with the load recorded. Outdoors, wind cools a hot connection and sun heats everything in its path, so note both, and grade outdoor findings with care. Our post on ΔT severity criteria covers how load and comparison method change a grade.

Write the settings down

A radiometric image stores its settings with the picture: emissivity, reflected temperature, distance and the other parameters the camera used. That makes the temperature checkable, and correctable, after you leave site.

Thermal image of a motor starter with the hottest overload heater at 63.6 degrees Celsius
A radiometric photo keeps its settings: this one was measured at an emissivity of 0.97, and the 63.6 °C box reading can be rechecked from the file at any time. HIKMICRO photo, DTI Suite SuperRes picture.

In DTI Suite's photo editor you can set the emissivity for a photo and the temperatures on it are recalculated, and each report page prints the parameters next to the measurements, so a reviewer can see exactly what a temperature was based on.

Questions

Why does shiny metal read the wrong temperature?
Clean or polished metal has a low emissivity: it gives off little infrared energy of its own and reflects a lot from its surroundings. The camera then reports a mix of the metal and its reflections. On a hot connection that usually means the reading is too low.
What emissivity should I use for electrical inspections?
Measure on high-emissivity surfaces, such as insulation, paint or tape, where a setting around 0.9 or above is typical, and avoid grading from bare metal. ASTM E1933 describes how to measure emissivity in the field when it matters.
How do I measure reflected temperature?
With the reflector method in ASTM E1862: place crumpled and flattened aluminium foil where the target is, set the camera to an emissivity of 1.0, and read the foil's average apparent temperature. Enter that as the reflected temperature.
Can temperatures be corrected after the inspection?
Yes, if the image is radiometric. The camera stores the settings with the image, so software can recalculate the temperatures with a corrected emissivity. A screenshot or exported picture cannot be corrected.